- Description: CM-ESS.MP Voltage monitoring relay 2c/o, B-C=3-600VRMS, 24-240VAC/DC
- Product ID: 1SVR740830R0500
- Extended Product Type: 1SVR740830R0500
- Product Net Weight: 0.143 kg
- Product Net Width: 22.5 mm
- Product Net Height: 85.6 mm
- Product Net Depth: 103.7 mm
- Degree of Protection: Housing IP50 Terminals IP20
- Ambient Air Temperature: Operation -20 ... +60 C Storage -40 ... +85 C
- Standards: EN 50178 IEC/EN 60255-27 IEC/EN 61000-6-2 IEC/EN 61000-6-3 UL 508 CAN/CSA C22.2 No.14
- Rated Impulse Withstand Voltage (U<sub>imp</sub>): Measuring Circuit / Output Circuit 6 kV Output Circuit 1 / Output Circuit 2 4 kV Supply Circuit / Measuring Circuit 6 kV Supply Circuit / Output Circuit 4 kV
- Rated Insulation Voltage (U<sub>i</sub>): Measuring Circuit / Output Circuit 600 V Output Circuit 1 / Output Circuit 2 250 V Supply Circuit / Measuring Circuit 600 V Supply Circuit / Output Circuit 250 V
- Terminal Type: Screwless Terminals
- Function: Over- or undervoltage monitoring
- Mounting on DIN Rail: TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
- eClass: 7.0 27371801
- Mounting Position: Any
- Mechanical Durability: 30000000 cycle
- Connecting Capacity: Flexible with Ferrule 2x 0.5 ... 1.5 mm Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm Flexible 2x 0.5 ... 1.5 mm Rigid 2x 0.5 ... 1.5 mm
- Maximum Operating Voltage UL/CSA: Output Circuit 300 V AC
- Overvoltage Category: III
- Connecting Capacity UL/CSA: Flexible 2x 18-16 AWG Rigid 2x 20-16 AWG
- Wire Stripping Length: 8 mm
- GL Certificate: GL_61765-14HH
- Short-Circuit Protective Devices: Output Circuit NC - F Type Fuses 10 A Output Circuit NO - F Type Fuses 10 A
- Rated Control Supply Voltage (U<sub>s</sub>): 24 ... 240 V AC/DC
- Output: 2 c/o (SPDT) contact; operating principle selectable
- Electrical Durability: AC-12 100000 cycle
- EAN: 4016779852418
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85364900
- Package Level 1 Width: 97 mm
- Package Level 1 Height: 109 mm
- Package Level 1 Length: 30 mm
- Package Level 1 Gross Weight: 0.165 kg
- Package Level 1 Units: 1 piece
- Measuring Range: 3 ... 30 V 6 ... 60 V 30 ... 300 V 60 ... 600 V
- Time Range: 0 s or 0.1-30 s tripping delay (ON)
- Rated Operational Current AC-12 (I<sub>e</sub>): (230 V) 4 A
- Rated Operational Current AC-15 (I<sub>e</sub>): (230 V) 3 A
- Rated Operational Current DC-12 (I<sub>e</sub>): (24 V) 4 A
- Rated Operational Current DC-13 (I<sub>e</sub>): (24 V) 2 A
- Minimum Switching Capacity: 24 V 10 mA
- Pollution Degree: 3
- RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
- Contact Rating UL/CSA: B300
- Instructions and Manuals: 1SVC730600M0000
- CB Certificate: CB_DK-28255-UL
- CCC Certificate: CCC_2007010303243843.pdf
- cULus Certificate: cULus508_20120203-E140448
- Data Sheet, Technical Information: 2CDC112173D0201
- Declaration of Conformity - CE: 1SVD981013-0000
- EAC Certificate: EAC_RU_C-DE.ME77.B.01012
- RMRS Certificate: RMRS_12.04009.250
- RoHS Information: 1SAA981056-4401
- E-nummer: 3860643
- ETIM 4: EC001438 - Voltage monitoring relay
- ETIM 5: EC001438 - Voltage monitoring relay
- ETIM 6: EC001438 - Voltage monitoring relay
- Object Classification Code: B
Santa Clara Systems specializes in hard-to-find parts. Choose from our overstock inventory and save on CM-ESS.MP . Santa Clara Systems carries 36,673 items from ABB.
- With Or Without Latching Function. The Hysteresis Is Adjustable Within A Range Of 3 To 30 % Of The Threshold Value. The Tripping Delay And The Start-Up Delay Are Adjustable Over A Range Of Instantaneous To 30 S (0
- 0.1-30 S). A Sealable Transparent Cover For Protection Against Unauthorized Changes Is Available As Accessory. The Device Offers Maintenance Free Easy Connect Technology With Push-In Terminals.
- The Cm-Ess.mp Is A Multifunctional Voltage Monitoring Relay From The Cm Single-Phase Monitors Range. This Monitoring Relay Operates With A Rated Control Supply Voltage Of 24 - 240 V Ac / Dc And Has A 2 C/o (Spdt) Output With Contacts Rated At 250 V / 4 A. It Provides A Rms Measuring Principle For Dc And Ac Voltages With 4 Measuring Ranges: 3-30 V
- 6-60 V
- 30-300 V And 60-600 V. The Cm-Ess.mp Offers Selection Of Over- Or Undervoltage Monitoring
- Open- Or Closed-Circuit Operating Principle
Alternates
- 1SVR740830R0500
- CM ESS.MP
- CMESS.MP
- CMESSMP
Common Typos
- CM-E55.MP
- CM-E5S.MP
- CM-ES5.MP
Appended Numbers
- CM-ESS.MP-A
- CM-ESS.MP-B
- CM-ESS.MP-C
- CM-ESS.MP-D
- CM-ESS.MP-E
- CM-ESS.MP-F
- CM-ESS.MP-G
- CM-ESS.MP-H
- CM-ESS.MP-I
- CM-ESS.MP-J
- CM-ESS.MP-K
- CM-ESS.MP-L
- CM-ESS.MP-M
- CM-ESS.MP-N
- CM-ESS.MP-O
- CM-ESS.MP-P
- CM-ESS.MP-Q
- CM-ESS.MP-R
- CM-ESS.MP-S
- CM-ESS.MP-T
- CM-ESS.MP-U
- CM-ESS.MP-V
- CM-ESS.MP-W
- CM-ESS.MP-X
- CM-ESS.MP-Y
- CM-ESS.MP-Z
Customers Are Also Buying
-
140M-C2E-B63
Allen Bradley
-
440R-D22R2
Allen Bradley
-
855P-B30ME22
Allen Bradley
We Deliver!
- ✓ Late West Coast Shipping (5PM PST)
- ✓ Drop-Ship and Blind-Ship Specialists
- ✓ Expertly Packed Static-Limited
- ✓ Same-Day Service
- ✓ In-House Courier