• ABB N40E-84 Contactor Relay Product Image
  • Abb N40E-84 Barcode

N40E-84

Product Summary:

  • Extended Product Type: N40E 110V 50Hz / 110-120V 60Hz
  • Product ID: 1SBH141001R8440
  • EAN: 3471522012845
  • Minimum Order Quantity: 1 piece
  • Customs Tariff Number: 85364900
Get a Quote
           or           
  • Description: Contactor Relay
  • Coil Consumption: Pull-in at Max. Rated Control Circuit Voltage 50 Hz 70 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 80 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 8 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 2 W Holding at Max. Rated Control Circuit Voltage 50 Hz 8 V·A Holding at Max. Rated Control Circuit Voltage 50 Hz 2 W Average Holding Value 50 / 60 Hz 8 V·A Average Holding Value 50 / 60 Hz 2 W Average Pull-in Value 50 Hz 74 V·A Average Pull-in Value 60 Hz 70 V·A
  • Operate Time: Between Coil Energization and NO Contact Closing 10 ... 26 ms Between Coil De-energization and NO Contact Opening 4 ... 11 ms
  • Connecting Capacity Auxiliary Circuit: Flexible with Cable End 0.75 ... 2.5 mm² Rigid Cable 1 ... 4 mm²
  • Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
  • Terminal Type: Screw Terminals
  • Climatic Withstand: acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
  • Maximum Operating Altitude Permissible: 3000 m
  • Resistance to Shock acc. to IEC 60068-2-27: Shock Direction: A 20 g Closed, Shock Direction: B1 10 g Open, Shock Direction: B1 5 g Shock Direction: B2 15 g Shock Direction: C1 20 g Shock Direction: C2 20 g
  • RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
  • Ambient Air Temperature: Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 °C Near Contactor for Operation in Free Air (Uc) -40 ... +70 °C Close to Contactor for Storage -60 ... +80 °C
  • Instructions and Manuals: FPTC407721P0001
  • BV Certificate: BV_2634H09651C0
  • CB Certificate: CB_FR_602227B
  • CCC Certificate: CCC_2003010304088235
  • CSA Certificate: CSA_1041746
  • cUL Certificate: UL_110105E48139A
  • Data Sheet, Technical Information: 1SBC100122C0202_Ch03
  • Declaration of Conformity - CE: 1SBD250808U1000
  • DNV Certificate: DNV-GL_TAE00000TY
  • GL Certificate: DNV-GL_TAE00000TY
  • GOST Certificate: GOST_POCCFRME01B03022
  • LR Certificate: LRS_9830010E2
  • RINA Certificate: RINA_ELE128713XG002
  • RMRS Certificate: RMRS_0507015250
  • RoHS Information: 1SBD350052R1000
  • UL Certificate: UL_110105E48139A
  • E-nummer: 3227603
  • ETIM 4: EC000196 - Contactor relay
  • ETIM 5: EC000196 - Contactor relay
  • ETIM 6: EC000196 - Contactor relay
  • UNSPSC: 39121500
  • Object Classification Code: K
  • Extended Product Type: N40E 110V 50Hz / 110-120V 60Hz
  • Product ID: 1SBH141001R8440
  • EAN: 3471522012845
  • Minimum Order Quantity: 1 piece
  • Customs Tariff Number: 85364900
  • EAN: 3471522012845
  • Product Net Depth: 74 mm
  • Product Net Height: 74 mm
  • Product Net Weight: 0.340 kg
  • Product Net Width: 44 mm
  • Package Level 1 Width: 78 mm
  • Package Level 1 Length: 79 mm
  • Package Level 1 Height: 47 mm
  • Package Level 1 Gross Weight: 0.34 kg
  • Package Level 1 EAN: 3471522012845
  • Package Level 2 Units: 63 piece
  • Package Level 3 Units: 1220 piece
  • Package Level 1 Units: 1 piece
  • Number of Auxiliary Contacts NO: 4
  • Number of Auxiliary Contacts NC: 0
  • Standards: Devices complying with international standards IEC 947-5-1 / 947-4-1 and European standards EN 60 947-5-1 / 60 947-4-1. Electromagnetic compatibility (EMC) according to amendment A11 to IEC 947-1; EN 60 947-1 and amendment 2 to IEC 947-4-1
  • Rated Operational Voltage: Main Circuit 690 V
  • Rated Frequency (f): Supply Circuit 50 Hz Supply Circuit 60 Hz
  • Conventional Free-air Thermal Current (Ith): acc. to IEC 60947-5-1, q = 40 °C 16 A
  • Rated Operational Current AC-15 (Ie): (220 / 240 V) 4 A (24 / 127 V) 6 A (380 / 440 V) 3 A (500 V) 2 A (690 V) 2 A
  • Short-Circuit Protective Devices: gG Type Fuses 10 A
  • Rated Short-time Withstand Current (Icw): for 0.1 s 140 A for 1 s 100 A
  • Rated Operational Current DC-13 (Ie): (125 V) 0.55 / 69 A (24 V) 6 / 144 A (250 V) 0.3 / 75 A (48 V) 2.8 / 134 A (72 V) 1 / 72 A
  • Rated Insulation Voltage (Ui): acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V acc. to UL/CSA 600 V
  • Rated Impulse Withstand Voltage (Uimp): 8 kV
  • Maximum Mechanical Switching Frequency: 6000 cycles per hour
  • Coil Operating Limits: (acc. to IEC 60947-5-1) 0.85 ... 1.1 x Uc (at ? ? 55 °C) °C
  • Rated Control Circuit Voltage (Uc): 50 Hz 110 V 60 Hz 110 120 V
Santa Clara Systems specialises in hard-to-find parts. Choose from our overstock inventory and save on N40E-84 . Santa Clara Systems carries 35,866 items from ABB.
We are in the process of adding data and downloadable material for this item. Please search similar items for more information related to this product.

Alternates

  • N40E-84

Common Types

  • N40E-B4
  • N4OE-84
  • N4OE-B4

Appended Numbers

  • N40E-84-A
  • N40E-84-B
  • N40E-84-C
  • N40E-84-D
  • N40E-84-E
  • N40E-84-F
  • N40E-84-G
  • N40E-84-H
  • N40E-84-I
  • N40E-84-J
  • N40E-84-K
  • N40E-84-L
  • N40E-84-M
  • N40E-84-N
  • N40E-84-O
  • N40E-84-P
  • N40E-84-Q
  • N40E-84-R
  • N40E-84-S
  • N40E-84-T
  • N40E-84-U
  • N40E-84-V
  • N40E-84-W
  • N40E-84-X
  • N40E-84-Y
  • N40E-84-Z

Customers Are Also Buying

We Deliver!

Late West Coast Shipping Hours
Late West Coast Shipping (5PM PST)
Drop-Ship and Blind-Ship Specialists
Expertly Packed Static-Limited
Same-Day Service
In-House Courier Domestic and International
visa credit card logo mastercard credit card logo discover credit card logo american express credit card logo